SECTION/RULE §554.320 - Lighting and Illumination
Chapter Review Date 03/11/2024

Current recommendations of the Illumination Engineering Society of North America must be followed to achieve proper illumination characteristics and lighting levels throughout the facility. Minimum illumination must be ten foot candles in resident rooms and 20 foot candles in corridors, nurses stations, dining rooms, lobbies, toilets, bathing facilities, laundries, stairways, and elevators. Illumination requirements for these areas apply to lighting throughout the space and should be measured at approximately 30 inches above the floor anywhere in the room. Minimum illumination for overbed reading lamps, medication preparation or storage areas, kitchens, and nurse's station desks must be 50 foot candles. Illumination requirements for these areas apply to the task performed and should be measured on the task.

Source Note: The provisions of this §554.320 adopted to be effective July 1, 1996, 21 TexReg 4408; transferred effective January 15, 2021, as published in the Texas Register December 11, 2020, 45 TexReg 8871.